Standard Guide for Selection and Use of Full-Encirclement-Type Band Clamps for Reinforcement or Repair of Punctures or Holes in Polyethylene Gas Pressure Pipe
NORMA vydaná dňa 1.8.2019
Označenie normy: ASTM F1025-19
Dátum vydania normy: 1.8.2019
Kód tovaru: NS-968897
Počet strán: 3
Približná hmotnosť: 9 g (0.02 libier)
Krajina: Americká technická norma
Kategória: Technické normy ASTM
Keywords:
damage, full-encirclement-type band clamp, hole, leak repair, pipe reinforcement, plastic pipe, puncture ,, ICS Number Code 21.060.70 (Clamps and staples)
Significance and Use | ||
4.1 Full-encirclement-type band clamps are recommended for repairs only where the pipe is able to maintain its structural integrity. These clamps are not recommended for permanent repair of pipe where the damage could propagate outside the clamp under anticipated field conditions (see 5.1.1 for repair limitations). In such situations, it is recommended to cut out and replace the damaged pipe with a new piece. Clamps that are used for repair should comply with the manufacturer’s specifications for use and the manufacturer’s installation instructions should be followed. 4.2 These clamps may be used to cover holes left in the pipe from abandoned service line connections, purge points, and accidental punctures. 4.3 These clamps may be used to reinforce the pipe where the wall thickness has been reduced because of gouges or other irregularities. 4.4 Some users reinforce polyethylene pipe after it has been squeezed-off as a precaution against pipe damage that may have occurred during the squeeze-off process and as a means of ensuring that the pipe will not be squeezed-off again at the same location. Consult with the polyethylene pipe manufacturer as to the appropriateness of squeeze-off for their product, and for circumstances when reinforcement is recommended. See Guide F1041. |
||
1. Scope | ||
1.1 This guide specifically addresses the design and installation of full-encirclement-type band clamps for repair of gouges, punctures, or holes, and for reinforcement of polyethylene plastic pipe. Guidelines are provided for selecting and using clamps in pipe sizes 2 in. nominal (60 mm) and larger. 1.1.1 A test method is also provided for the user to assess the applicability of the repair clamp. Under appropriate circumstances, this type of clamp offers a convenient, effective, and safe means of restoring the integrity of an in-service pipeline, without cutting out a section of pipe (see Note 1). The pipe to be repaired cannot be backed by a stiffener for internal support and cross-sectional dimensional control. Satisfactory use of this type of clamp should rely on the crush resistance of the pipe itself and a fitting design concept, which retains the cross-sectional pipe configuration while minimizing compressive forces required to obtain an effective leakage seal. Note 1: The appropriateness for use of this type of clamp
should be determined by using the information contained in this
guide and from consultation with, and recommendations of, both the
pipe and clamp manufacturers. The basic premise for use of this
type of clamp is that it is recommended by the manufacturer for
this specific application and that step-by-step installation
instructions are available for that application. It is important in
the development of this type of clamp that prototype testing be
conducted to evaluate performance expectations because of the
physical limitations encountered when designing it for use with
plastic pipe.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||
2. Referenced Documents | ||
|