Standard Test Method for 2,6-di-tert-Butyl- p-Cresol and 2,6-di-tert-Butyl Phenol in Electrical Insulating Oil by Infrared Absorption
NORMA vydaná dňa 1.12.2021
Označenie normy: ASTM D2668-07(2021)
Dátum vydania normy: 1.12.2021
Kód tovaru: NS-1046335
Počet strán: 6
Približná hmotnosť: 18 g (0.04 libier)
Krajina: Americká technická norma
Kategória: Technické normy ASTM
Keywords:
2,6-ditertiary-butyl paracresol, 2,6-ditertiary-butyl phenol, electrical insulating oil, infrared absorption,, ICS Number Code 29.040.10 (Insulating oils)
Significance and Use | ||||||
3.1?The quantitative determination of 2,6-ditertiary-butyl paracresol and 2,6-ditertiary-butyl phenol in a new electrical insulating oil measures the amount of this material that has been added to the oil as protection against oxidation. In a used oil it measures the amount remaining after oxidation has reduced its concentration. The test is also suitable for manufacturing control and specification acceptance. 3.2?When an infrared spectrum is obtained of an electrical insulating oil inhibited with either of these compounds there is an increase in absorbance of the spectrum at several wavelengths (or wavenumbers). 2,6 ditertiary-butyl paracresol produces pronounced increases in absorbance at 2.72 ?m (3650 cm?1), and 11.63 ?m (860 cm?1 ). 2,6 ditertiary-butyl phenol produces pronounced increases in absorbance at 2.72 ?m (3650 cm?1) and 13.42 ?m (745 cm ?1). 3.3?When making this test on other than a highly oxidized oil or when using a double-beam spectrophotometer, it has been found convenient to obtain the spectrum between 2.5 ?m (4000 cm?1) and 2.9 ?m (3450 cm?1) because the instrument is compensated for the presence of moisture and the band is not influenced by intermolecular forces (associations). However, when testing a highly oxidized oil or when using a single-beam instrument better results may be obtained if the scan is made between 10.90 ?m (918 cm?1) and 14.00 ?m (714 cm?1). 3.4?Increased absorption at 11.63 ?m (860 cm ?1) or 13.42 ?m (745 cm?1) or both, will identify the inhibitor as 2,6-ditertiary-butyl paracresol or 2,6-ditertiary-butyl phenol respectively (Note 1). Note 1:?The absorbance at 745 cm?1 for
2,6-ditertiary-butyl phenol and at 860 cm?1 for
2,6-ditertiary-butyl paracresol for equal concentrations will be in
the approximate ratio of 2.6 to 1.
|
||||||
1. Scope | ||||||
1.1?This test method covers the determination of the weight percent of 2,6-ditertiary-butyl paracresol (DBPC) and 2,6-ditertiary-butyl phenol (DBP) in new or used electrical insulating oil in concentrations up to 0.5 % by measuring its absorbance at the specified wavelengths in the infrared spectrum. 1.2?The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. 1.3?This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.4?This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||||||
2. Referenced Documents | ||||||
|