Potrebujeme váš súhlas na využitie jednotlivých dát, aby sa vám okrem iného mohli ukazovať informácie týkajúce sa vašich záujmov. Súhlas udelíte kliknutím na tlačidlo „OK“.
Standard Test Method for Oxidation Stability of Mineral Insulating Oil
NORMA vydaná dňa 1.11.2021
Označenie normy: ASTM D2440-13(2021)
Dátum vydania normy: 1.11.2021
Kód tovaru: NS-1043753
Počet strán: 5
Približná hmotnosť: 15 g (0.03 libier)
Krajina: Americká technická norma
Kategória: Technické normy ASTM
Keywords:
acid, aging, electrical oil, insulating mineral oil, oxidation, sludge, stability, transformer ,, ICS Number Code 29.040.10 (Insulating oils)
Significance and Use | ||||||||||||||
4.1?The oxidation stability test of mineral transformer oils is a method for assessing the amount of sludge and acid products formed in a transformer oil when the oil is tested under prescribed conditions. Good oxidation stability is necessary in order to maximize the service life of the oil by minimizing the formation of sludge and acid. Oils that meet the requirements specified for this test in Specification D3487 tend to minimize electrical conduction, ensure acceptable heat transfer, and preserve system life. There is no proven correlation between performance in this test and performance in service, since the test does not model the whole insulation system (oil, paper, enamel, wire). However, the test can be used as a control test for evaluating oxidation inhibitors and to check the consistency of oxidation stability of production oils. |
||||||||||||||
1. Scope | ||||||||||||||
1.1?This test method determines the resistance of mineral transformer oils to oxidation under prescribed accelerated aging conditions. Oxidation stability is measured by the propensity of oils to form sludge and acid products during oxidation. This test method is applicable to new oils, both uninhibited and inhibited, but is not well defined for used or reclaimed oils. Note 1:?A shorter duration oxidation test for evaluation of
inhibited oils is available in Test Method D2112.
Note 2:?For those interested in the measurement of volatile
acidity, reference is made to IEC Method 61125. 2
1.2?The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. 1.3?This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.4?This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||||||||||||||
2. Referenced Documents | ||||||||||||||
|
Posledná aktualizácia: 2024-11-24 (Počet položiek: 2 206 712)
© Copyright 2024 NORMSERVIS s.r.o.